LEO KM

Flowair


Poder Térmico:
Color:
VERSION:
Tamanho Conduta:

Payments: Pagamento acto da entrega
Dimensions: Width: 0cm; Height: 0cm; Depth: 0cm
Weight: 39.7 Kg

SHORT CHARACTERISTIC:

LEO KM mixing chamber is designed to work with fan heaters LEO FB 25/45/65/95. It enables delivery of fresh (outside) air into the room. Depending on the requirements, the air flow can be heated via the heat exchanger and then directed inside the building.

The chamber is equipped with three air intakes: 2 of recirculation air and one of fresh air. It is possible to smoothly adjust the degree of dampers opening from 0 to 100%. Thanks to this it is possible to recover heat by recirculation.

LEO KM is available in three versions: KM S, KM L i KM 95


LEO KM with fan heater, UVO roof fans and KM REGULATION system create complete mechanical ventilation system. More information about complete heating and ventilation solutions for buildings can be found in FLOWAIR System menu.

.

PURPOSE:

LEO KM with fan heaters can be applied in medium and big cubature buildings like industrial halls, warehouses, commercial halls, etc.

CONTROL SYSTEM:

KM REGULATION – complete control and protection set for LEO KM + LEO FB..

TECHNOLOGY/INNOVATION/BENEFITS:

Construction – modular construction (3 parts) makes possible to install the unit in various configurations. This solution gives various installation options.

Casing of the heater is made of light and durable material – expanded polypropylene (EPP).

Unit is in standard equipped with EU3 class filter (EU4 class filter is an option) installed on air inlet. Its position determines filtration of fresh air or fresh and recirculation air. 

Specifications of LEO KM
Sku
LKM

Technical data LEO KM + LEO FB

LEO FB 10V +LEO KM S LEO FB 20V + LEO KM S LEO FB 30V + LEO KM S LEO FB 25V + LEO KM L LEO FB 45V + LEO KM L LEO FB 65V + LEO KM L LEO FB 95V + LEO KM 95
Fan LEO FB V + LEO KM – Axial, single-phase, AC, 3 speed fan
Filter class EU3
Max. air flow [m3/h] 1750 1600 1500 3200 3000 2800 6500
Power supply [V/Hz] 230/50
Max. current consumption [A] 0.5 0.5 0.5 1.4 1.4 1.4 2.8
Max. power consumption [W] 110 110 110 320 320 320 640
IP / Insulation class 54/F
Max. acoustic pressure level [dB(A)]** 47 47 47 54 54 54 57
Max. air flow range [m]* 12.0 11.0 10.0 18.0 16.5 15.5 25.0
Heat exchanger Cu - Al.,
S ingle row
Cu – Al.,
two row
Cu – Al.,
two row
Cu - Al.,
S ingle row
Cu – Al.,
two row
Cu – Al.,
three row
Cu – Al.,
two row
Nominal heating power *** [kW ] 9.2 18.7 23.3 24.2 37.3 52.0 87.0
Air temperature increase (ΔT )*** [oC] 15.5 34.5 46.0 22.5 37.0 55.5 39.5
Max. heating water temperature [oC] 120
Max. operating pressure [MPa] 1.6
Connection [”] 1/2 3/4
Type of casing steel + aluminum
Color Grey*****
Usage Inside buildings
Maximum operational temperature [oC] 50 60
Position of operation  Can be installed in any desired position
Weight of unit [kg] 25.9 26.8 27.9 34.3 35.5 37.8 70.2
Weight of unit filled with water [kg] 26.6 28 29.3 35.3 37.5 40.5 73.7

* Performance without air intake. With air intake, the performance drop by approximately 10%
** Acoustic pressure level at a distance of 5 m from the unit, in the room of medium capabillity of sound absorption and 1500 m3 of cubic measure.
***Range of horizontal isothermal air stream, at 0,5 m/s velocity limit
**** At Maximum air stream flow, temperature of heating medium 90/70°C, temperature at the inlet to the device 0°C
*****Available in any RAL color on request

MAIN DIMENSIONS LEO KM + LEO FB

km

 

Heating capacities LEO KM + LEO FB

LEO FB 10 + KM S
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
V = 800 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 (2) (2) (2)
-20 7,1 127 0,3 6,5 7,5 330 1,6 8,0
-15 6,8 120 0,2 10,0 7,1 313 1,5 11,5 6,2 273 1,2 8,0
-10 6,4 113 0,2 13,5 6,7 297 1,3 15,0 5,8 256 1,1 11,5
-5 6,0 107 0,2 17,5 6,3 280 1,2 18,5 5,4 239 0,9 15,0
0 5,6 100 0,2 21,0 6,0 263 1,1 22,0 5,0 221 0,8 18,5
5 5,2 93 0,2 24,0 5,6 245 1,0 25,5 4,6 204 0,7 22,0
10 4,8 86 0,1 27,5 5,2 228 0,8 29,0 4,2 186 0,6 25,5
15 4,4 78 0,1 31,0 4,8 211 0,7 32,5 3,8 169 0,5 29,0
20 4,0 70 0,1 34,5 4,4 193 0,6 36,0 3,4 151 0,4 32,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 (2) (2) (2)
-20
-15
-10 4,9 214 0,8 8,0 4,0 351 2,0 5,0
-5 4,5 197 0,7 11,5 3,5 153 0,5 8,0 3,6 317 1,7 8,5
0 4,1 179 0,6 15,0 3,1 134 0,4 11,5 3,2 282 1,4 12,0
5 3,7 161 0,5 18,5 2,6 113 0,3 14,5 2,8 246 1,1 15,5
10 3,3 143 0,4 22,0 2,0 86 0,2 17,5 2,4 210 0,8 19,0
15 2,8 124 0,3 25,5 1,7 72 0,1 21,0 2,0 172 0,6 22,0
20 2,4 103 0,2 28,5 1,4 60 0,1 25,0 1,5 132 0,4 25,5
V = 1200 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 (2) (2) (2)
-20
-15 8,5 150 0,4 6,0 8,9 394 2,2 7,0
-10 8,0 142 0,3 10,0 8,5 373 2,0 11,0 7,3 322 1,6 8,0
-5 7,5 134 0,3 13,5 8,0 352 1,8 14,5 6,8 300 1,4 12,0
0 7,1 125 0,3 17,5 7,5 330 1,6 18,5 6,3 279 1,2 15,5
5 6,6 117 0,2 21,0 7,0 309 1,4 22,0 5,8 257 1,1 19,5
10 6,1 108 0,2 25,0 6,6 287 1,2 26,0 5,3 235 0,9 23,0
15 5,6 99 0,2 28,5 6,0 265 1,1 29,5 4,8 213 0,8 27,0
20 5,1 90 0,2 32,0 5,5 243 0,9 33,5 4,3 190 0,6 30,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 (2) (2) (2)
-20
-15
-10 6,2 270 1,2 5,5
-5 5,7 248 1,0 9,0 4,5 194 0,7 6,0 4,6 399 2,6 6,5
0 5,2 226 0,9 13,0 3,9 171 0,6 9,5 4,1 355 2,1 10,0
5 4,7 204 0,7 16,5 3,4 147 0,4 13,5 3,6 311 1,6 14,0
10 4,1 181 0,6 20,0 2,8 121 0,3 17,0 3,0 265 1,2 17,5
15 3,6 158 0,5 24,0 1,9 83 0,2 19,5 2,5 219 0,9 21,0
20 3,1 134 0,4 27,5 1,6 69 0,1 24,0 2,0 171 0,6 25,0
V = 1750 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 (2) (2) (2)
-20
-15
-10 9,8 173 0,4 6,5 10,4 458 2,9 7,5 9,0 395 2,3 5,5
-5 9,2 163 0,4 10,5 9,8 432 2,6 11,5 8,4 369 2,0 9,0
0 8,6 153 0,4 14,5 9,2 405 2,3 15,5 7,8 342 1,8 13,0
5 8,0 143 0,3 18,5 8,5 379 2,1 19,5 7,2 315 1,5 17,0
10 7,4 132 0,3 22,5 8,0 352 1,8 23,5 6,6 288 1,3 21,0
15 6,8 121 0,2 26,5 7,4 325 1,6 27,5 6,0 261 1,1 25,0
20 6,2 111 0,2 30,5 6,8 298 1,3 31,0 5,3 233 0,9 29,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 (2) (2) (2)
-20
-15
-10
-5 7,0 305 1,5 7,0
0 6,4 278 1,3 11,0 4,9 212 0,8 8,0 5,0 437 3,0 8,5
5 5,7 251 1,1 14,5 4,2 183 0,6 12,0 4,4 382 2,4 12,5
10 5,1 223 0,9 18,5 3,5 153 0,5 16,0 3,8 327 1,8 16,5
15 4,5 195 0,7 22,5 2,8 120 0,3 19,5 3,1 271 1,3 20,0
20 3,8 166 0,5 26,5 1,8 77 0,1 23,0 2,5 213 0,8 24,0

In order to get parameters of devices operating with mediums at different temperature please contact our sales department

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

(2) Not allowed, too low temperature at the outlet of the devices

LEO FB 20 + KM S
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
V = 550 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 12,7 225 1,2 43,5 12,2 537 6,3 41 10,9 479 5,3 34
-20 12,1 215 1,1 45,5 12 512 5,8 42,5 10,3 453 4,8 36
-15 11,5 205 1,0 47,5 11 486 5,3 44,5 9,7 428 4,4 37,5
-10 11,0 195 0,9 49,0 10,4 460 4,8 46,5 9,1 402 3,9 39,5
-5 10,4 185 0,8 51,0 9,8 435 4,4 48 8,6 376 3,5 41
0 9,8 175 0,7 53,0 9,3 409 3,9 50 8 351 3,1 43
5 9,3 164 0,7 54,5 8,7 384 3,5 51,5 7,4 325 2,7 44,5
10 8,7 154 0,6 56,5 8,1 358 3,1 53,5 6,8 299 2,3 46,5
15 8,1 144 0,5 58,0 7,5 332 2,7 55 6,2 273 2 48
20 7,5 134 0,5 59,5 6,9 305 2,3 57 5,6 246 1,6 49,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 9,6 421 4,4 27 8,3 363 3,5 20 8 701 11,6 18,5
-20 9 395 3,9 29 7,7 337 3,1 22 7,5 650 10,1 20,5
-15 8,4 370 3,5 30,5 7,1 311 2,7 23,5 6,9 600 8,7 22
-10 7,9 344 3,1 32,5 6,5 286 2,3 25,5 6,3 549 7,4 24
-5 7,3 318 2,7 34 6 260 1,9 27 5,7 497 6,3 26
0 6,7 292 2,3 36 5,3 234 1,6 29 5,1 446 5,2 27,5
5 6,1 267 2 37,5 4,7 207 1,3 30,5 4,5 394 4,2 29
10 5,5 240 1,6 39,5 4,1 180 1 32 3,9 342 3,2 31
15 4,9 214 1,3 41 3,5 152 0,7 33,5 3,3 289 2,4 32,5
20 4,2 186 1 42,5 2,8 123 0,5 35 2,7 235 1,7 34,5
V = 1000 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 18,7 333 2,3 31,0 18,2 806 13,1 29,5 16,3 718 11 23,5
-20 17,9 318 2,2 33,5 17,4 768 12 31,5 15,5 680 10 26
-15 17,1 303 2,0 36,0 16,5 730 11 34 14,6 642 9 28,5
-10 16,2 289 1,8 38,0 15,6 692 9,9 36,5 13,7 604 8 31
-5 15,4 274 1,6 40,5 14,8 653 9 39 12,8 565 7,2 33
0 14,5 259 1,5 43,0 13,9 615 8,1 41 12 527 6,3 35,5
5 13,7 244 1,3 45,5 13 576 7,2 43,5 11,1 488 5,5 38
10 12,8 228 1,2 48,0 12,1 537 6,3 46 10,2 449 4,7 40
15 12,0 213 1,1 50,0 11.3 498 5,5 48 9,3 409 4 42,5
20 11,1 198 0,9 52,5 10,4 458 4,8 50 8,4 369 3,3 44,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 14,4 631 9 18 12,5 544 7,2 12,2 12,1 1054 24 11
-20 13,5 593 8,1 20 11,6 506 6,3 14,5 11,2 978 21 13,5
-15 12,6 555 7,2 22,7 10,7 467 5,5 17 10,3 902 18,1 15,5
-10 11,8 516 6,3 25 9,8 429 4,7 19 9,5 825 15,5 18
-5 10,9 478 5,5 27,5 8,9 390 4 21,5 8,6 748 13 20,5
0 10 439 4,7 29,5 8 351 3,3 23,8 7,7 671 10,7 23
5 9,1 400 4 32 7,1 312 2,7 26 6,8 593 8,6 25
10 8,2 361 3,3 34 6,2 272 2,1 28,5 5,9 514 6,6 27,5
15 7,3 321 2,7 36,5 5,3 231 1,6 30,5 5 434 4,9 29,5
20 6,4 280 2,1 38,5 4,3 188 1,1 32,5 4 354 3,4 32

In order to get parameters of devices operating with mediums at different temperature please contact our sales department

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

(2) Not allowed, too low temperature at the outlet of the devices

LEO FB 25 + KM L
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
V = 1600 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 22,1 392 1,5 16,0 20,1 885 6,7 12,5 17,8 784 5,7 8,0
-20 21,0 374 1,4 19,0 19,1 843 6,3 15,5 16,9 741 5,1 11,5
-15 20,0 356 1,3 22,0 18,1 800 5,7 18,5 15,9 699 4,6 14,5
-10 19,0 338 1,2 25,5 17,2 757 5,2 22,0 14,9 656 4,1 17,0
-5 18,0 319 1,0 28,5 16,2 714 4,6 25,0 13,9 612 3,6 21,0
0 16,9 301 0,9 31,5 15,2 671 4,2 28,0 12,9 569 3,2 24,0
5 15,9 282 0,8 34,5 14,2 627 3,7 31,0 12,0 525 2,8 27,0
10 14,8 263 0,7 37,0 13,2 583 3,2 34,5 10,9 480 2,4 30,0
15 13,7 244 0,7 40,0 12,2 538 2,8 37,5 9,9 435 2,0 33,5
20 12,6 224 0,6 43,0 11,2 493 2,4 40,5 8,9 390 1,6 36,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 (2) (2) (2)
-20 14,6 640 4,1 7,0
-15 13,6 597 3,6 10,5 11,3 494 2,7 6,0 12,0 1040 10,3 7,0
-10 12,7 554 3,1 13,5 10,3 451 2,3 9,0 10,9 948 8,7 10,5
-5 11,7 510 2,7 16,5 9,3 407 1,9 12,5 9,8 856 7,2 13,5
0 10,7 466 2,3 19,5 8,3 362 1,5 15,5 8,8 765 5,9 16,5
5 9,6 422 1,9 23,0 7,3 316 1,2 18,5 7,7 671 4,7 19,0
10 8,6 377 1,6 26,0 6,2 270 0,9 21,5 6,6 577 3,6 22,0
15 7,6 331 1,3 29,0 5,1 221 0,6 24,5 5,5 481 2,6 25,0
20 6,5 285 1,0 32,0 3,8 166 0,4 27,0 4,4 385 1,7 28,0
V = 2500 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 28,1 499 2,3 10,0 25,4 1120 10,5 6,6 (2)
-20 26,8 476 2,1 13,5 24,2 1066 9,6 10,0 21,3 938 7,8 6,5
-15 25,5 453 2,0 16,5 22,9 1012 8,8 13,5 20,1 883 7,0 10,0
-10 24,2 430 1,8 20,0 21,5 957 7,9 17,0 18,9 829 6,3 13,5
-5 22,9 406 1,6 23,5 20,5 903 7,1 20,5 17,6 774 5,5 17,0
0 21,5 383 1,5 26,5 19,2 848 6,3 23,5 16,4 719 4,8 20,0
5 20,2 359 1,3 30,0 18,0 793 5,6 27,0 16,1 706 4,7 25,0
10 18,8 335 1,1 33,0 16,7 737 4,9 30,5 14,7 646 4 28,0
15 17,5 310 1,0 36,5 15,4 680 4,3 34,0 13,3 586 3,4 31,5
20 16,1 286 0,9 39,5 14,1 623 3,6 37,0 11,9 525 2,8 34,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 (2) (2) (2)
-20
-15 18,4 803 6,1 8,0
-10 17,0 745 5,3 11,0 13,9 607 3,8 7,0 14,3 1243 14,2 7,0
-5 15,7 686 4,6 14,5 12,6 548 3,2 10,5 12,9 1123 11,8 10,5
0 14,3 627 3,9 17,5 11,2 488 2,6 14,0 11,5 1001 9,6 13,5
5 13,0 568 3,3 21,0 9,8 427 2,1 17,0 10,1 879 7,6 17,0
10 11,6 507 2,7 24,0 8,4 365 1,6 20,5 8,7 756 5,8 20,0
15 10,2 446 2,1 27,5 6,9 302 1,1 23,5 7,3 631 4,2 23,5
20 8,8 384 1,6 30,5 5,4 235 0,7 26,5 5,8 505 2,8 26,5
V = 3200 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 33,1 589 3,1 6,0 (2) (2)
-20 31,6 562 2,9 8,0 30,4 1343 14,7 8,5
-15 30,1 534 2,6 13,0 28,9 1274 13,3 12,0 25,3 1112 10,7 8,5
-10 28,5 507 2,4 16,5 27,3 1206 12,0 15,5 23,7 1043 9,5 12,0
-5 27,0 479 2,2 20,0 25,8 1137 10,8 19,0 22,2 974 8,4 15,5
0 25,4 451 1,9 23,5 24,2 1068 9,7 22,5 20,6 905 7,4 19,0
5 23,8 423 1,7 27,0 22,6 998 8,5 26,0 19,0 835 6,4 22,5
10 22,2 395 1,5 30,5 21,0 927 7,5 29,5 17,4 764 5,4 26,0
15 20,6 366 1,3 34,0 19,4 856 6,5 33,0 15,8 692 4,5 29,5
20 18,9 336 1,2 37,5 17,8 784 5,5 36,5 14,1 620 3,7 33,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 (2) (2) (2)
-20
-15
-10 20,1 881 7,2 8,5 16,5 718 5,2 5,5 16,5 1437 18,5 5,5
-5 18,5 811 6,2 12,0 14,9 648 4,3 9,0 14,9 1297 15,4 8,5
0 17,0 742 5,3 15,5 13,2 577 3,5 12,5 13,3 1157 12,5 12,5
5 15,3 671 4,4 19,0 11,6 506 2,8 15,5 11,7 1015 9,9 15,5
10 13,7 600 3,6 22,5 9,9 433 2,1 19,0 10,3 872 7,5 19,0
15 12,1 527 2,9 26,0 8,2 358 1,5 22,5 8,4 728 5,4 22,5
20 10,4 454 2,2 29,5 6,4 281 1,0 26,0 6,7 583 3,6 26,0

In order to get parameters of devices operating with mediums at different temperature please contact our sales department

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

(2) Not allowed, too low temperature at the outlet of the devices

LEO FB 30 + KM S
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
V = 300 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 9,5 169 0,4 69,5 9,0 399 2,0 65,0 8,1 356 1,6 55,5
-20 9,1 161 0,3 70,0 8,6 380 1,8 65,5 7,7 337 1,5 56,0
-15 8,6 153 0,3 70,5 8,2 361 1,6 66,0 7,2 317 1,4 56,5
-10 8,2 145 0,3 71,0 7,7 341 1,5 66,5 6,8 298 1,2 57,0
-5 7,7 137 0,3 71,5 7,3 322 1,3 67,0 6,3 278 1,1 57,5
0 7,3 129 0,2 71,5 6,9 303 1,2 67,5 5,9 259 0,9 58,0
5 6,8 121 0,2 72,0 6,4 283 1,1 68,0 5,5 240 0,8 58,5
10 6,4 113 0,2 72,5 6,0 264 0,9 68,5 5,0 220 0,7 59,0
15 5,9 105 0,2 72,5 5,5 245 0,8 69,0 4,6 201 0,6 59,5
20 5,4 97 0,1 72,5 5,1 226 0,7 69,5 4,1 181 0,5 60,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 7,1 312 1,4 46,0 6,2 268 1,1 36,0 6,0 522 3,6 34,5
-20 6,7 293 1,2 46,5 5,7 249 1,0 36,5 5,6 483 3,1 35,0
-15 6,2 273 1,1 47,0 5,3 229 0,8 37,0 5,1 445 2,7 35,5
-10 5,8 254 1,0 47,5 4,8 209 0,7 37,5 4,7 406 2,3 36,3
-5 5,4 234 0,8 48,0 4,3 189 0,6 38,0 4,2 368 1,9 37,0
0 4,9 215 0,7 48,5 3,9 168 0,5 38,0 3,8 329 1,6 37,5
5 4,5 195 0,6 49,0 3,4 147 0,4 38,0 3,3 290 1,3 38,0
10 4,0 175 0,5 49,0 2,8 123 0,3 38,0 2,9 250 1,0 38,0
15 3,5 155 0,4 49,5 2,4 102 0,2 38,0 2,4 210 0,7 38,5
20 3,1 133 0,3 49,5 2,0 86 0,2 39,0 1,9 168 0,5 39,0
V = 800 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 20,2 359 1,4 50,0 19,8 872 8,0 48,5 17,6 775 6,6 41,0
-20 19,3 343 1,3 51,5 18,8 830 7,3 50,0 16,7 733 6,0 42,0
-15 18,3 326 1,2 53,0 17,8 787 6,6 51,0 15,7 691 5,4 43,5
-10 17,4 309 1,1 54,5 16,9 745 6,0 52,5 14,8 648 4,8 45,0
-5 16,4 292 1,0 56,0 15,9 702 5,4 54,0 13,8 606 4,3 46,0
0 15,5 276 0,9 57,5 15,0 660 4,8 55,5 12,8 564 3,9 47,5
5 14,5 259 0,8 58,5 14,0 618 4,3 56,5 11,9 521 3,3 49,0
10 13,6 242 0,7 60,0 13,0 576 3,8 58,0 10,9 479 2,8 50,0
15 12,7 225 0,6 61,0 12,1 533 3,3 59,0 9,9 436 2,4 51,5
20 11,7 208 0,5 62,5 11,1 491 2,8 60,5 9,0 394 2,0 52,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 15,5 679 5,4 33,0 13,4 583 4,3 25,0 13,1 1140 14,6 24,0
-20 14,6 637 4,8 34,0 12,4 541 3,8 26,0 12,1 1056 12,7 25,0
-15 13,6 595 4,3 35,5 11,4 498 3,2 27,5 11,2 971 10,9 26,5
-10 12,6 552 3,8 37,0 10,5 456 2,8 29,0 10,2 887 9,3 28,0
-5 11,6 510 3,3 38,0 9,5 413 2,3 30,0 9,2 802 9,2 29,0
0 10,7 467 2,8 39,5 8,5 370 1,9 31,4 8,2 718 6,3 30,5
5 9,7 424 2,3 41,0 7,5 326 1,5 32,5 7,3 632 5,1 32,0
10 8,7 382 1,9 42,0 6,5 282 1,2 34,0 6,3 547 3,9 33,0
15 7,7 338 1,6 43,5 5,4 236 0,9 35,0 5,3 460 2,9 34,5
20 6,7 295 1,2 44,5 4,3 188 0,6 35,5 4,3 373 2,0 35,5
V = 1500 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 30,9 549 3,0 36,5 30,9 1360 17,9 36,0 27,5 1208 14,8 29,5
-20 29,4 523 2,8 38,5 29,3 1294 16,3 38,0 26,0 1142 13,4 31,5
-15 28,0 498 2,6 40,5 27,8 1228 14,9 40,0 24,5 1076 12,0 33,5
-10 26,5 472 2,3 42,5 26,3 1161 13,4 42,0 23,0 1010 10,7 35,5
-5 25,1 446 2,1 44,5 24,8 1095 12,1 44,0 21,5 944 9,5 37,5
0 23,7 421 1,9 46,5 23,3 1029 10,8 46,0 20,0 878 8,3 39,5
5 22,2 395 1,7 48,5 21,8 963 9,6 48,0 18,5 811 7,2 41,5
10 20,8 369 1,5 50,5 20,3 896 8,4 50,0 17,0 744 6,2 43,0
15 19,3 343 1,3 52,5 18,8 830 7,3 51,5 15,4 678 5,2 45,0
20 17,8 317 1,1 54,5 17,3 764 6,3 53,5 13,9 611 4,3 47,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 24,2 1057 12,0 23,0 20,8 906 9,5 16,5 20,5 1780 32,6 15,5
-20 22,5 991 10,7 25,0 19,3 841 8,3 18,5 19,0 1648 28,4 17,5
-15 21,2 925 9,5 27,0 17,8 774 7,1 20,5 17,4 1517 24,4 19,5
-10 19,6 859 8,3 29,0 16,3 708 6,1 22,0 15,9 1384 20,7 21,5
-5 18,1 793 7,2 31,0 14,7 642 5,1 24,0 14,4 1252 17,2 23,5
0 16,6 726 6,1 33,0 13,2 575 4,2 26,0 12,9 1119 14,1 25,5
5 15,1 660 5,2 34,5 11,6 507 3,4 28,0 11,3 986 11,2 27,5
10 13,5 593 4,2 36,5 10,1 439 2,6 30,0 9,8 851 8,6 29,0
15 12,0 525 3,4 38,5 8,5 370 1,9 31,5 8,2 716 6,3 31,0
20 10,5 457 2,7 40,0 6,9 298 1,3 33,5 6,7 580 4,3 33,0

In order to get parameters of devices operating with mediums at different temperature please contact our sales department

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

(2) Not allowed, too low temperature at the outlet of the devices

LEO FB 45 + KM L
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
V = 1250 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 29,6 526 1,3 45,5 27,6 1217 6,2 40,5 24,6 1083 5,2 33,5
-20 28,2 502 1,2 47,0 26,3 1159 5,7 42,5 23,3 1024 4,7 35,5
-15 26,9 478 1,1 49,0 24,9 1100 5,2 44,5 22,0 965 4,2 37,0
-10 25,6 454 1,9 50,5 23,6 1041 4,7 46,0 20,6 907 3,8 39,0
-5 24,2 430 0,9 52,5 22,3 982 4,2 48,0 19,3 848 3,4 41,0
0 22,9 406 0,8 54,0 20,9 924 3,8 49,5 18,0 789 3,0 42,5
5 21,5 382 0,8 56,0 19,6 965 3,4 51,3 16,6 730 2,6 44,0
10 20,1 358 0,7 57,5 18,2 805 3,0 53,0 15,2 670 2,2 46,0
15 18,7 333 0,6 59,0 16,9 745 2,6 54,5 13,9 609 1,9 47,5
20 17,3 308 0,5 60,5 15,5 684 2,2 56,5 12,5 548 1,6 49,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 21,7 948 4,3 26,5 18,7 814 3,4 19,5 15,6 1355 8,5 21,5
-20 20,3 890 3,8 28,5 17,3 755 3,0 21,5 14,4 1256 7,5 23,0
-15 19,0 831 3,4 30,0 16,0 696 2,6 23,0 13,3 1156 6,4 24,5
-10 17,7 772 3,0 32,0 14,6 637 2,2 25,0 12,1 1056 5,5 26,0
-5 16,3 713 2,6 33,5 13,3 577 1,8 26,5 11,0 956 4,6 27,5
0 14,9 654 2,2 35,5 11,9 517 1,5 28,0 9,8 855 3,8 29,0
5 13,6 594 1,9 37,0 10,5 456 1,2 29,5 8,7 754 3,0 30,5
10 12,2 534 1,5 38,5 9,0 394 0,9 31,5 7,5 652 2,3 32,0
15 10,8 473 1,2 40,5 7,5 330 0,7 33,0 6,3 549 1,7 33,5
20 9,4 410 1,0 42,0 6,0 261 0,5 34,0 5,1 444 1,2 35,0
V = 2050 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 41,2 732 2,4 35,0 38,6 1703 11,5 31,0 34,5 1514 9,5 25,0
-20 39,3 699 2,2 37,0 36,7 1621 10,5 33,5 32,6 1432 8,6 27,5
-15 37,4 666 2,0 39,4 34,9 1539 9,5 35,5 30,7 1350 7,8 29,5
-10 35,6 632 1,8 41,5 33,0 1457 8,6 38,0 28,9 1268 6,9 32,0
-5 33,7 599 1,7 44,0 31,1 1374 7,8 40,0 27,0 1185 6,1 34,0
0 47,7 848 2,2 69,0 29,3 1292 7,0 42,5 26,1 1103 5,4 36,0
5 31,8 566 1,5 46,0 27,4 1209 6,2 44,5 23,2 1020 4,7 38,5
10 29,9 532 1,3 48,0 25,5 1126 5,4 46,5 21,3 936 4,0 40,5
15 26,1 465 1,1 52,5 23,6 1041 4,7 49,0 19,4 851 3,4 43,0
20 24,2 431 0,9 54,5 21,7 956 4,0 51,0 17,4 766 2,8 45,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 30,3 1325 7,8 19,0 26,1 1137 6,1 13,0 25,6 2228 20,9 12,5
-20 28,4 1244 6,9 21,5 24,2 1055 5,4 15,0 23,7 2065 18,2 14,5
-15 26,6 1162 6,1 23,5 22,3 973 4,6 17,5 21,8 1901 15,7 16,5
-10 24,7 1079 5,4 26,0 20,4 890 4,0 19,5 20,0 1736 13,3 19,0
-5 22,8 997 4,7 28,0 18,5 807 3,3 22,0 18,1 1571 11,1 21,0
0 20,9 914 4,0 30,0 16,6 723 2,7 24,0 16,2 1405 9,1 23,5
5 19,0 830 3,4 32,5 14,7 639 2,2 26,0 14,2 1238 7,3 25,5
10 17,0 746 2,8 34,5 12,7 553 1,7 28,0 12,3 1071 5,6 27,5
15 15,1 660 2,2 36,5 10,7 465 1,3 30,5 10,4 902 4,1 30,0
20 13,1 574 1,7 38,5 8,6 374 0,9 32,5 8,4 731 2,8 32,0
V = 3000 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 52,3 929 3,7 27,0 49,2 2169 17,8 24,0 43,9 1928 14,8 18,5
-20 49,9 887 3,4 29,5 46,8 2065 16,3 26,5 41,5 1823 13,4 21,0
-15 47,5 845 3,1 32,0 44,4 1960 14,8 29,0 39,1 1719 12,0 24,0
-10 45,1 803 2,8 34,5 42,0 1856 14,4 31,5 36,7 1614 10,7 26,5
-5 42,8 760 2,6 37,5 39,7 1750 12,1 34,0 34,3 1509 9,5 29,0
0 40,4 718 2,3 40,0 37,3 1645 10,8 37,0 31,9 1404 8,3 31,5
5 38,0 675 2,1 42,5 34,9 1540 9,6 39,5 29,5 1298 7,2 34,0
10 35,5 632 1,8 45,0 32,5 1433 8,4 42,0 27,1 1191 6,2 36,5
15 33,1 588 1,6 47,5 30,0 1326 7,3 44,5 26,6 1083 5,2 39,0
20 30,6 543 1,4 50,0 27,6 1217 6,2 47,0 22,2 974 4,3 41,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 38,6 1687 12,0 13,5 33,2 1447 9,4 8,0 32,7 2841 32,5 7,5
-20 36,2 1583 10,7 16,0 30,8 1343 8,2 10,5 30,3 2633 28,3 10,0
-15 33,8 1479 9,5 18,5 28,4 1238 7,1 13,0 27,9 2424 24,4 12,5
-10 31,4 1374 8,3 21,0 26,0 1133 6,1 16,0 25,4 2213 20,7 15,0
-5 29,0 1268 7,2 23,5 23,6 1027 5,1 18,5 23,0 2003 17,2 18,0
0 26,6 1163 6,1 26,0 21,1 921 4,2 21,0 20,6 1791 14,1 20,5
5 24,1 1056 5,2 29,0 18,7 813 3,4 23,5 18,1 1578 11,2 23,0
10 21,7 948 4,3 31,5 16,2 704 2,6 26,0 15,7 1364 8,6 25,5
15 19,2 840 3,4 34,0 13,6 593 1,9 28,5 13,2 1148 6,4 28,0
20 16,7 729 2,7 36,5 11,0 479 1,3 30,5 10,7 930 4,4 30,5

In order to get parameters of devices operating with mediums at different temperature please contact our sales department

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

(2) Not allowed, too low temperature at the outlet of the devices

LEO FB 65 + KM L
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
V = 1000 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 35,4 629 1,3 80,5 31,2 1379 5,6 68,0 28,1 1234 4,7 58,5
-20 33,9 603 1,2 81,0 29,8 1314 5,1 68,5 26,6 1170 4,3 59,5
-15 32,4 576 1,1 81,5 28,3 1250 4,7 69,0 25,2 1106 3,9 60,0
-10 30,9 549 1,0 81,5 26,9 1186 4,2 70,0 23,7 1042 3,5 60,5
-5 29,4 523 0,9 82,0 25,4 1122 3,8 70,5 22,2 977 3,1 61,0
0 27,9 496 0,9 82,5 24,0 1058 3,5 71,0 20,1 913 2,7 61,5
5 26,4 469 0,8 83,0 22,5 994 3,1 71,5 19,3 849 2,4 62,0
10 24,9 442 0,7 83,0 21,1 929 2,7 72,0 17,8 784 2,1 62,5
15 23,3 414 0,6 83,0 19,6 864 2,4 72,5 16,3 718 1,8 63,0
20 21,7 386 0,6 83,5 18,1 799 2,1 73,0 14,8 651 1,5 63,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 24,9 1091 3,9 49,0 21,7 946 3,1 39,5 20,5 1785 9,9 36,0
-20 23,5 1026 3,5 50,0 20,2 881 2,8 40,0 19,0 1658 8,7 36,5
-15 22,0 962 3,1 50,5 18,7 816 2,4 40,5 17,6 1531 7,6 37,0
-10 20,5 897 2,8 51,0 17,2 751 2,1 41,0 16,1 1403 6,5 38,0
-5 19,0 833 2,4 51,5 15,7 686 1,8 41,5 14,7 1276 5,5 38,5
0 17,6 768 2,1 52,0 14,2 619 1,5 42,0 13,2 1148 4,5 39,0
5 16,1 703 1,8 52,5 12,7 552 1,2 42,5 11,7 1019 3,7 39,5
10 14,5 636 1,5 53,0 11,1 483 1,0 42,5 10,2 888 2,9 40,0
15 13,0 569 1,2 53,0 9,5 411 0,7 43,0 8,7 756 2,2 40,5
20 11,4 500 1,0 53,5 7,7 334 0,5 42,5 7,1 621 1,5 40,5
V = 1750 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 54,3 965 2,8 67,5 48,6 2146 12,4 58,0 43,6 1918 10,4 49,5
-20 52,0 924 2,6 68,5 46,3 2045 11,3 59,0 41,4 1817 9,4 50,5
-15 49,6 882 2,4 69,5 44,1 1944 10,3 60,0 39,1 1716 8,5 51,5
-10 47,3 841 2,2 70,0 41,8 1843 9,4 61,0 36,8 1615 7,6 52,5
-5 44,9 799 2,0 71,0 39,5 1742 8,5 62,0 34,5 1514 6,8 53,5
0 42,6 757 1,8 72,0 37,2 1642 7,6 63,0 32,2 1413 6 54,5
5 40,3 716 1,6 73,0 34,9 1541 6,8 64,0 29,9 1312 5,2 55,5
10 37,9 672 1,5 73,5 32,6 1439 6,0 65,0 27,5 1210 4,5 56,5
15 35,4 630 1,3 74,5 30,3 1337 5,3 66,0 25,2 1106 3,9 57,0
20 33,0 586 1,2 75,0 27,9 1233 4,5 66,5 22,8 1002 3,2 57,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 38,6 1690 8,5 41,0 33,6 1463 6,8 32,0 32,0 2785 22,2 29,5
-20 36,3 1590 7,7 42,0 31,2 1362 6,0 33,0 29,7 2585 19,4 30,5
-15 34,0 1489 6,8 43,0 28,9 1260 5,2 34,0 27,4 2385 16,8 31,5
-10 31,7 1387 6,0 44,0 26,6 1159 4,5 35,0 25,1 2184 14,3 32,5
-5 29,4 1286 5,2 45,0 24,2 1056 3,8 36,0 22,8 1983 12,0 33,5
0 27,1 1185 4,5 46,0 21,9 953 3,2 37,0 20,5 1782 9,9 34,5
5 24,7 1082 3,8 47,0 19,5 849 2,6 38,0 18,2 1580 8,0 35,5
10 22,4 979 3,2 47,5 17,1 743 2,1 38,5 15,8 1750 6,3 36,5
15 20,0 874 2,6 48,5 14,6 634 1,6 39,5 13,4 1167 4,7 37,5
20 17,5 767 2,1 49,5 12,0 521 1,1 40,0 11,0 957 3,3 38,5
V = 2800 m3/h 
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 75,6 1345 5,1 55,5 68,6 3026 23,1 48,0 61,5 2700 19,3 40,5
-20 72,4 1286 4,7 57,0 65,3 2883 21,2 49,5 58,2 2557 17,5 42,0
-15 69,1 1228 4,3 58,5 62,1 2739 19,3 51,0 54,9 2414 15,8 43,5
-10 65,8 1169 4,0 60,0 58,8 2596 17,5 52,5 51,7 2271 14,1 45,0
-5 62,5 1110 3,6 61,0 55,6 2453 15,8 54,0 48,4 2127 12,5 46,5
0 59,2 1052 3,3 62,5 52,0 2310 14,1 55,5 45,2 1984 11,0 47,5
5 55,8 993 2,9 64,0 49,1 2166 12,6 56,5 41,9 1840 9,6 49,0
10 52,5 933 2,6 65,0 45,8 2021 11,1 58,0 38,6 1694 8,3 50,5
15 49,1 872 2,3 66,5 42,5 1875 9,7 59,5 35,2 1547 7,1 52,0
20 45,6 810 2,0 67,5 39,2 1728 8,4 61,0 31,8 1399 5,9 53,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 54,3 2376 15,8 33,0 47,1 2052 12,6 25,0 (2)
-20 51,0 2233 14,1 34,5 43,8 1909 11,0 26,5 42,0 3651 36,3 24,5
-15 47,8 2090 12,5 36,0 40,5 1766 9,6 28,0 38,7 3366 31,3 26,0
-10 44,5 1946 11,0 37,0 37,2 1622 8,2 29,5 35,4 3081 26,7 27,5
-5 41,2 1803 9,6 38,5 33,9 1477 7,0 31,0 32,1 2795 22,4 29,0
0 37,9 1659 8,3 40,0 30,6 1331 5,8 32,5 28,8 2509 18,4 30,5
5 34,6 1514 7,0 41,5 27,2 1185 4,7 33,5 25,5 2221 14,8 32,0
10 31,2 1367 5,8 43,0 23,8 1035 3,7 35,0 22,2 1929 11,5 33,0
15 27,8 1218 4,7 44,0 20,3 883 2,8 36,5 18,8 1635 8,5 34,5
20 24,4 1068 3,8 45,5 16,7 726 2,0 37,5 15,8 1337 6,0 36,0

 In order to get parameters of devices operating with mediums at different temperature please contact our sales department

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

(2) Not allowed, too low temperature at the outlet of the devices

LEO FB 95 + KM 95
Tp1 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2 PT Qw ∆pw Tp2
°C kW l/h kPa °C kW l/h kPa °C kW l/h kPa °C
V = 2650 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 67,9 1206 3,6 51,5 62,4 2753 16,6 45,0 55,9 2455 13,9 38,0
-20 64,9 1153 3,3 53,0 59,4 2622 15,2 47,0 52,9 2324 12,6 39,5
-15 61,9 1100 3,0 54,5 56,4 2490 13,8 48,5 49,9 2193 11,3 41,0
-10 58,9 1046 2,8 56,0 53,5 2359 12,5 50,0 46,9 2062 10,1 42,5
-5 55,9 993 2,5 57,5 50,5 2227 11,3 51,5 43,9 1930 9,0 44,0
0 52,9 940 2,3 59,0 47,5 2096 10,1 53,0 40,9 1799 7,9 45,5
5 49,9 886 2,1 60,5 44,5 1965 9,0 54,5 37,9 1667 6,9 47,5
10 46,8 832 1,8 62,0 41,5 1832 7,9 56,0 34,9 1533 5,9 49,0
15 43,7 777 1,6 63,5 38,5 1698 6,9 57,5 31,8 1399 5,0 50,5
20 40,6 721 1,4 65,0 35,4 1563 5,9 59,0 28,8 1263 4,2 52,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 49,4 2160 11,3 30,5 42,8 1865 9,0 23,0 41,4 3599 30,2 21,5
-20 46,4 2029 10,1 32,0 39,8 1734 7,9 24,5 38,4 3339 26,3 23,0
-15 43,4 1898 9,0 33,5 36,8 1603 6,9 26,5 35,4 3077 22,7 25,0
-10 40,4 1766 7,9 35,5 33,8 1471 5,9 28,0 32,4 2815 19,3 26,0
-5 37,4 1635 6,9 37,0 30,7 1339 5,0 29,5 27,9 2553 16,2 28,0
0 34,3 1503 5,9 38,5 27,7 1206 4,1 31,0 26,3 2289 13,3 29,5
5 31,3 1370 5,0 40,0 24,6 1073 3,4 32,5 23,3 2025 10,7 31,0
10 28,3 1236 4,2 41,5 21,5 937 2,6 34,0 20,2 1759 8,3 32,5
15 25,2 1100 3,4 43,0 18,3 798 2,0 35,5 17,2 1492 6,2 34,0
20 22,0 963 2,7 44,5 15,1 658 1,4 36,5 14,0 1222 4,3 35,5
V = 4420 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 96,4 1713 6,7 40,0 89,0 3928 31,8 35,0 79,7 3501 26,5 28,5
-20 92,1 1638 6,2 42,0 84,8 3741 29,1 37,0 75,4 3315 24,0 31,0
-15 87,9 1562 5,7 44,0 80,5 3554 26,5 39,0 71,2 3128 21,5 33,0
-10 83,6 1486 5,2 46,0 76,3 3366 24,0 41,5 66,9 2940 19,3 35,0
-5 79,3 1410 4,7 48,5 72,0 3179 21,6 43,5 62,6 2752 17,1 37,0
0 75,1 1334 4,3 50,5 67,8 2991 19,3 45,5 58,4 2565 15,0 39,0
5 70,8 1258 3,8 52,5 63,5 2803 17,2 47,5 54,1 2376 13,1 41,0
10 66,4 1180 3,4 54,0 59,2 2613 15,1 49,5 49,7 2185 11,2 43,0
15 62,0 1102 3,0 56,0 54,9 2421 13,1 51,5 45,4 1993 9,5 45,0
20 57,6 1023 2,7 58,0 50,5 2228 11,3 53,5 40,9 1799 7,9 47,0
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 70,3 3078 21,6 22,5 60,9 2656 17,1 16,0 (2)
-20 66,1 2892 19,3 24,5 56,7 2470 15,0 18,0
-15 61,8 2705 17,1 26,5 52,4 2283 13,0 20,5 50,5 4395 43,3 19,0
-10 57,5 2517 15,0 28,5 48,1 2095 11,1 22,5 46,2 4020 36,9 21,0
-5 53,2 2329 13,0 30,5 43,7 1907 9,4 24,5 41,9 3645 30,9 23,0
0 48,9 2141 11,2 32,8 39,4 1717 7,8 26,5 37,6 3268 25,3 25,0
5 44,6 1951 9,4 35,0 35,0 1526 6,3 28,5 33,2 2889 20,3 27,0
10 40,2 1759 7,8 37,0 30,6 1333 4,9 30,5 28,8 2509 15,7 29,0
15 35,8 1566 6,4 39,0 26,1 1136 3,7 32,5 24,4 2126 11,6 31,0
20 31,3 1370 5,0 40,5 21,5 936 2,6 34,0 20,0 1740 8,1 33,0
V = 6500 m3/h
Tw1/Tw2 = 120/70°C Tw1/Tw2 = 90/70°C Tw1/Tw2 = 80/60°C
-25 123,3 2193 10,5 31,5 (2) 102,3 4494 41,9 22,0
-20 117,9 2096 9,7 34,0 108,9 4804 46,1 30,0 96,8 4255 37,9 24,5
-15 112,5 1999 8,9 36,5 103,4 4564 42,0 32,5 91,4 4015 34,0 27,0
-10 107,0 1902 8,1 39,0 98,0 4323 38,0 35,0 85,9 3774 30,4 29,5
-5 101,5 1804 7,4 41,5 92,5 4082 34,2 37,0 80,4 3533 26,7 31,5
0 96,0 1707 6,7 43,5 87,0 3841 30,5 39,5 74,9 3291 23,7 34,0
5 90,5 1609 6,0 46,0 81,5 3599 27,1 42,0 69,4 3049 20,6 36,5
10 84,9 1509 5,3 48,5 76,0 3354 23,8 44,5 63,8 2803 17,6 39,0
15 79,3 1409 4,7 51,0 70,4 3107 20,7 47,0 58,2 2556 14,9 41,5
20 73,5 1307 4,1 53,0 64,8 2858 17,8 49,0 52,5 2306 12,4 43,5
Tw1/Tw2 = 70/50°C Tw1/Tw2 = 60/40°C Tw1/Tw2 = 50/40°C
-25 90,3 3950 34,0 16,5 78,2 3407 26,8 11,0 (2)
-20 84,8 3711 30,3 19,0 72,7 3168 23,5 13,5
-15 79,3 3470 26,8 21,5 67,2 2928 20,4 16,0
-10 73,8 3229 23,5 24,0 61,6 2687 17,4 18,0
-5 68,3 2988 20,4 26,0 56,1 2444 14,7 20,5
0 62,7 2745 17,5 28,5 50,5 2201 12,2 23,0 48,3 4198 39,9 22,0
5 57,2 2502 14,8 31,0 44,9 1956 9,8 25,5 42,7 3711 31,9 24,5
10 51,5 2255 12,3 33,5 39,2 1707 7,7 28,0 37,0 3221 22,8 27,0
15 45,9 2006 9,9 35,5 33,4 1455 5,8 30,0 31,4 2728 18,2 29,0
20 40,1 1755 7,8 38,0 27,5 1199 4,1 32,5 25,6 2230 12,7 31,5

 In order to get parameters of devices operating with mediums at different temperature please contact our sales department

V – air flow
PT – heating capacity
Tp1 – inlet air temperature
Tp2 – outlet air temperature
Tw1 – inlet water temperature
Tw2 – outlet water temperature
Qw – water stream flow in the heat exchanger
Δpw – water pressure drop in heat exchanger

(2) Not allowed, too low temperature at the outlet of the devices

The heating and ventilation units LEO KM L + LEO FB can be installed on the walls or under the ceiling in any position. The basic equipment of the unit consists of the brackets for installation under the ceiling using pins. 

km

The additional elements for installation of LEO KM L + LEO FB are:

Installation brackets – enable installation on vertical partitions.

Flexible adapter – ensures easy installation of the unit to the air intake or further duct installation and prevents possible vibration.


We present also some installation tips below:

km

  Steady air circulation should be provided in the entire room.

km

It is not recommended to supply the fresh air by ducts with may cause additional local pressure losses. It may cause a significant decrease of efficiency.

km

  It is allowed to supply the fresh air to the unit by straight ducts.

km

 Big objects must not limit the air stream of the heater.

km

  Heaters installed on the opposite walls should be overlapped.

km

 Heaters should be installed in a way that ensures free air supply                
 around the unit.

UVO H is the group of roof fans with horizontal air outlet. They are designed for ventilation of public and industrial buildings. Their main function is to remove stale air from the room.
 

Combined with LEO FB and LEO KM create complete mechanical ventilation system.

Our cookie policy

We use cookies to give you the best possible experience on our website. Learn More